DING Hong-jun FAN Dian YAO Hao-wei. Cable tunnel fire experiment based on linear temperature sensing fire detectors[J]. Editorial Office of Optics and Precision Engineering, 2013,21(9): 2225-2230
DING Hong-jun FAN Dian YAO Hao-wei. Cable tunnel fire experiment based on linear temperature sensing fire detectors[J]. Editorial Office of Optics and Precision Engineering, 2013,21(9): 2225-2230 DOI: 10.3788/OPE.20132109.2225.
Cable tunnel fire experiment based on linear temperature sensing fire detectors
The engineering suitability of typical linear heat detectors for early fire detection in cable tunnels was explored. In cable tunnel environments
an experimental platform was established based on exiting linear temperature fire detectors
including temperature sensing cables
fiber Raman detectors and fiber grating detectors
then two different fire experimental scenes were set up
and the temperature variation and fire detector response time were recorded in the processing of fire simulation. The experiments show that only directly contacting heat detectors can give an alarm response and other non-contact detectors are unable to respond the small-scale fire because a small amount of thermal radiation has no flame for the beginning of the fire. Furthermore
for massive fire
the alarm response time of both fiber Raman sensing heat fire detector and fiber grating sensing fire detector is about 30 s
the temperature over the fire recorded by a thermocouple is less than 35 ℃ in 60 s
while the temperature rising is more than 5 ℃/min within the range of 3 m. According to the technical characteristics of the three detectors
the engineering suitability of the typical linear heat detectors in cable tunnels early fire detection is analyzed
which can provide technical support for establishing the design specifications of fire alarm.
关键词
Keywords
references
UDD E, SPILLMAN Jr W B. Fiber Optic Sensors: an Introduction for Engineers and Scientists [M]. John Wiley & Sons, Inc., 2011.[2]ISHIIA H, KAWAMURAA K, ONOA T, et al.. A fire detection system using optical fibres for utility tunnels [J]. Fire Safety Journal, 1997, 29(2-3):87-98.[3]朱军, 范典. 光纤光栅隧道火灾探测器的设计研究[J]. 武汉理工大学学报, 2007, 29(4):107-109.ZHU J, FAN D. Design of fiber bragg grating detector in tunnel fire [J]. Journal of Wuhan University of Technology, 2007, 29(4):107-109. (in Chinese)[4]GB50414-2007 钢铁冶金企业设计防火规范[S]. 北京: 中国计划出版社, 2007.GB50414-2007 code of design on fire protection and prevention for iron & steel metallurgy enterprises [S]. Beijing: China Planning Press, 2007. (in Chinese)[5]GB50229-2006 火力发电厂与变电站设计防火规范[S]. 北京: 中国计划出版社, 2007.GB50229-2006 code for design of fire protection for fossil fuel power plants and substations [S]. Beijing: China Planning Press, 2007. (in Chinese)[6]GB/T21197-2007线型光纤感温火灾探测器[S]. 北京: 中国标准出版社, 2007.GB/T21197-2007 line type optical fiber heat detectors [S]. Beijing: Standards Press of China, 2007. (in Chinese)[7]GB16280-2005 线型感温火灾探测器[S]. 北京: 中国标准出版社, 2005.GB16280-2005 line type heat fire detectors [S]. Beijing: Standards Press of China, 2005. (in Chinese)[8]EN 54-22:2007 fire detection and fire alarm system-Part 22: line type heat detectors [S]. European Committee of Standardization.[9]张杨, 陈启军. 常用隧道火灾探测器原理、应用及研究动态[J]. 地下空间与工程学报, 2006, 2(2):311-314.ZHANG Y, CHEN Q J. Principles application and future development of conventional tunnel fire detectors [J]. Chinese Journal of Underground Space and Engineering, 2006, 2(2):311-314. (in Chinese)[10]ZHANG Z, JIN SH ZH, WANG J F, et al.. Recent progress in distributed optical fiber Raman sensors[C]. Proceedings of 22nd International Conference on Optical Fiber Sensors, Beijing, 2012:84210L-1-11.[11]KASHYAP R. Fiber Bragg Grattings [M]. Elsevier Inc., 2010.